Document Citation: Wis. Adm. Code PSC 135.181

Header:
WISCONSIN ADMINISTRATIVE CODE
PUBLIC SERVICE COMMISSION
CHAPTER PSC 135 GAS SAFETY
SUBCHAPTER II -- ADDITIONS TO 49 CFR PART 192


Date:
08/31/2009

Document:

PSC 135.181 Distribution line valves addition [49 CFR 192.181].

After 49 CFR 192.181(b), insert:

(bw) The distance between the valve and the regulator or regulators shall be sufficient to permit the operation of the valve during an emergency such as a large gas leak or a fire in the station. These valves shall be in accessible locations neither closer than 25 feet nor more than 1,500 feet distant from each regulator station.