Document Citation:
Wis. Adm. Code PSC 135.181
Header:
WISCONSIN ADMINISTRATIVE CODE
PUBLIC SERVICE COMMISSION
CHAPTER PSC 135 GAS SAFETY
SUBCHAPTER II -- ADDITIONS TO 49 CFR PART 192
Date:
08/31/2009
Document:
PSC 135.181 Distribution line valves addition [49 CFR 192.181].
After 49 CFR 192.181(b), insert:
(bw) The distance between the valve and the regulator or regulators shall be sufficient to permit the operation of the valve during an emergency such as a large gas leak or a fire in the station. These valves shall be in accessible locations neither closer than 25 feet nor more than 1,500 feet distant from each regulator station.